SPECIFICATION SHEET β€’ SI METRIC
CAT: THERMO

Boiler Efficiency & Fuel Rate

Estimate useful boiler heat duty, fuel input, thermal efficiency, and specific steam fuel consumption from steam and fuel measurements.

OPERATING LIMITS β€” Direct boiler heat-balance calculation only; reconcile HHV/LHV basis, blowdown, auxiliary loads, radiation, unburned fuel, and the applicable boiler test code before reporting efficiency.
INPUT DESIGN PARAMETERS (SI)
kg/h
kJ/kg
kJ/kg
kg/h
MJ/kg
CALCULATED SPECIFICATION OUTPUT
Useful Steam Heat Duty
3277.78 kW
Fuel Input Duty4151.39 kW
Boiler Thermal Efficiency78.96 %
Specific Fuel Consumption0.07 kg fuel / kg steam

Technical Methodology & Engineering Principles

GOVERNING EQUATION
Useful heat = steam flow Γ— (steam enthalpy βˆ’ feedwater enthalpy); fuel input = fuel flow Γ— heating value; efficiency = useful heat / fuel input Γ— 100.
Assumptions & Scope

Steady-state direct efficiency screen; enthalpies and heating value are entered on a consistent basis. Account for blowdown, radiation, unburned fuel, auxiliary power, and HHV/LHV convention in a full boiler test.

Operating Range & Boundary

Use finite, physically meaningful inputs within the stated operating assumptions.