SPECIFICATION SHEET β€’ SI METRIC
CAT: WATER-SLURRY

Water Treatment Chemical Dosing

Calculate active chemical mass, prepared solution mass, and dosing-pump volume from water flow, target dose, concentration, and solution density.

OPERATING LIMITS β€” Chemical feed-rate calculation only; validate jar-test demand, residual targets, solution strength, density, calibration, materials compatibility, injection hydraulics, and handling requirements.
INPUT DESIGN PARAMETERS (SI)
mΒ³/h
mg/L
%
kg/L
CALCULATED SPECIFICATION OUTPUT
Active Chemical Rate
πŸ’§
24 kg/day
Prepared Solution Mass192 kg/day
Dosing Solution Volume174.55 L/day

Related planning checklists

This calculator appears in the following engineering planning checklists:

1. Plant Water Balance Calculator2. Wastewater Hydraulic Retention Time3. Water Treatment Chemical Dosing4. Sedimentation Tank Sizing5. Rectangular Tank Volume & Capacity6. Freshwater vs Recycled Water Ratio

Technical Methodology & Engineering Principles

GOVERNING EQUATION
Active chemical per day = water flow Γ— dose; solution mass = active mass / active fraction; solution volume = solution mass / solution density.
Assumptions & Scope

Steady water flow and uniform dosing. Verify jar-test demand, residual targets, chemical compatibility, temperature, calibration-cylinder volume, injection quill hydraulics, and local handling requirements.

Operating Range & Boundary

Use finite, physically meaningful inputs within the stated operating assumptions.