INPUT DESIGN PARAMETERS (SI)
m³/h
m
1
CALCULATED SPECIFICATION OUTPUT
Hydraulic Power (Phyd)
💧24.52 kW
| Hydraulic Power (HP) | 32.89 HP |
Pump H-Q and system resistance curves
DUTY POINT: 200 m³/h @ 45 m TDHRelated planning checklists
This calculator appears in the following engineering planning checklists:
Water Utility Pump Station & Energy Audit
Plant Operations Manager1. Plant Water Balance Calculator2. Pipe Velocity & Diameter Sizing3. Reynolds Number Calculator4. Pipe Pressure Loss Calculator5. Static & Total Dynamic Head (TDH)6. Pump Hydraulic Power Calculator7. Pump Operating Energy Cost Calculator
Rectangular Tank & Water Transfer Pump Check
Mechanical Engineer1. Rectangular Tank Volume & Capacity2. Pipe Velocity & Diameter Sizing3. Reynolds Number Calculator4. Pipe Pressure Loss Calculator5. Static & Total Dynamic Head (TDH)6. Pump Hydraulic Power Calculator7. Pump Operating Energy Cost Calculator
Technical Methodology & Engineering Principles
GOVERNING EQUATION
Phyd (kW) = (Q (m³/h) × H (m) × SG × 9.81) / 3600
Assumptions & Scope
100% ideal hydraulic energy transfer without mechanical loss.
Operating Range & Boundary
Use finite, physically meaningful inputs within the stated operating assumptions.