SPECIFICATION SHEET • SI METRIC
CAT: HVAC

Cooling Tower Makeup & Blowdown

Calculate evaporation loss, blowdown rate, and total makeup water requirement for industrial cooling towers based on cycles of concentration.

OPERATING LIMITS — Cooling-tower water-balance calculation; account for drift, chemistry, cycles and operating range.
INPUT DESIGN PARAMETERS (SI)
m³/h
°C
1
CALCULATED SPECIFICATION OUTPUT
Total Makeup Water
24 m³/h
Evaporation Loss18 m³/h
Blowdown Rate6 m³/h

Related planning checklists

This calculator appears in the following engineering planning checklists:

1. Factory Air Exchange & Ventilation2. Industrial Chilled Water Cooling Capacity (HVAC)3. Cooling Tower Makeup & Blowdown

Technical Methodology & Engineering Principles

GOVERNING EQUATION
Evaporation = circulation × range × 0.0018 per °C (0.001 per °F); blowdown = evaporation/(cycles − 1); makeup = evaporation + blowdown.
Assumptions & Scope

Rule-of-thumb evaporation factor with drift and other losses omitted. Cycles exceed one; chemistry, ambient psychrometrics, heat load, drift eliminator performance, and water treatment are not modeled.

Operating Range & Boundary

Circulation and temperature range must be non-negative; cycles of concentration must be greater than one.