Airflow Sensible Cooling Load

Estimate sensible cooling capacity from air volume flow, air density, specific heat, and temperature difference.

💡 Engineering Knowledge PrimerSensible air-side cooling load is the mass flow multiplied by air specific heat and dry-bulb temperature difference. Latent load, infiltration, solar gains, envelope gains, occupancy, and equipment heat are outside this first-pass screen.
OPERATING LIMITS — Sensible-only cooling calculation; add latent, envelope, infiltration, solar, occupancy, equipment, and psychrometric loads before HVAC selection.
INPUT DESIGN PARAMETERS (SI)
m³/h
kg/m³
°C
kJ/kg·K
CALCULATED SPECIFICATION OUTPUT
Sensible Cooling Capacity
33.5 kW
Cooling Capacity9.53 TR
Air Mass Flow12000 kg/h

Related planning checklists

This calculator appears in the following engineering planning checklists:

1. Factory Air Exchange & Ventilation2. Duct Diameter from Airflow & Velocity3. Fan Power from Airflow & Static Pressure4. Airflow Sensible Cooling Load

Technical Methodology & Engineering Principles

GOVERNING EQUATION
SI: Q (kW) = [Airflow (m³/h) / 3600] × ρ × Cp × ΔT US: Q (Btu/h) = CFM × ρ (lb/ft³) × Cp (Btu/lb·°F) × ΔT × 60
Assumptions & Scope

Sensible-only steady flow; constant air properties; no latent, envelope, infiltration, radiation, or equipment-load terms.

Operating Range & Boundary

Airflow, density, temperature difference, and specific heat must be positive.